Up to 88.0% efficiency
Full power from -10°C to +50°C operation at 230Vac @ 5000 meters or 16400 feet altitude
Built-in DC OK relay contact option available
Compliance to SEMI F47 @ 200Vac
Conformal coating on PCBAs to protect against common dust and chemical pollutants

Dimensions (L x W x D) : | 123.6 x 40 x 117.6 mm |
| 4.87" x 1.57" x 4.63" |
Unit Weight : | 0.54 kg (1.19 lb) |
Nominal Output Voltage 24V |
Output Voltage Adjustment Range 22-28Vdc |
Output Current 5A |
Output Power 120W |
Line Regulation < 0.5% (@ 85-264Vac, 100% load) |
Load Regulation < 1% (0-100% load) |
PARD (20mhz) < 120mVpp @ > -10°C to +70°C < 240mVpp @ ≤ -10°C to -20°C |
Start-up Time 200ms typ. @ 115Vac & 230Vac (100% load) |
Hold-up Time 20ms typ. @ 115Vac (100% load) 90ms typ. @ 230Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage) ± 10% @ 85-264Vac input, 0-100% load (Slew Rate: 0.1A/μs) |
Start-up with Capacitive Loads 8,000μF Max |
Nominal Input Voltage 100-240Vac |
Input Voltage Range 85-264Vac |
Nominal Input Frequency 50-60Hz |
Input Frequency Range 47-63Hz |
DC Input Voltage Range 120-375Vdc |
Input Current 2.2A typ. @ 115Vac, 1.2A typ. @ 230Vac |
Efficiency at 100% load 85% typ. @ 115Vac, 88% typ. @ 230Vac |
Max Inrush Current 20A typ. @ 115Vac, 40A typ. @ 230Vac |
Leakage Current < 0.25mA @ 264Vac |
Case Cover / Chassis SGCC / Aluminium |
Dimensions 123.6 x 40 x 117.6 mm 4.87" x 1.57" x 4.63" |
Unit Weight 0.54 kg (1.19 lb) |
Indicator Green LED (DC OK) |
Cooling System Convection |
Input Terminal 3 Pins (Rated 600V/35A) |
Output Terminal DRL-24V120W1AA: 4 Pins (Rated 300V/28A) DRL-24V120W1AS: 6 Pins (Rated 300V/28A) |
Noise Sound Pressure Level (SPL) Sound Pressure Level (SPL) < 25dBA (1 Meter from p |
Mounting Rail Standard TS35 DIN Rail in accordance with EN 60715 |
Wire Input: AWG 18-8 Output: AWG 24-12 |
Surrounding Air Temperature operating -20°C to +70°C |
Surrounding Air Temperature storage -40°C to +85°C |
Power De-rating -10°C to -20°C de-rate power by 2%/°C > 40°C de-rate power by 1.67% / °C @ 115Vac > 50°C de-rate power by 2.5% / °C @ 230Vac < 100Vac de-rate power by 1% / Vac |
Operating Humidity 5 to 95% RH (Non-Condensing) |
Shock Test (Non-Operating) IEC 60068-2-27, 27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total |
Shock (Operating) IEC 60068-2-27, 27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis |
Vibration Test (Non-Operating) IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions |
Vibration (Operation) IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s? (2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for X direction |
Overvoltage 28.8V-35.2V, SELV Output, Latch Mode |
Overload / Overcurrent 105-150% of rated load current, Continuous current |
Over Temperature Latch Mode |
Short Circuit Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed) |
Degree of Protection IP20 |
Protection Against Shock Class I with Primary Earth connection |
MTBF
Telcordia SR-332: > 700,000 hrs
I/P: 100Vac, O/P: 100% load, Ta: 25°C
Electrical Safety TUV Bauart: EN 60950-1 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881) CCC: GB4943.1 CB scheme: IEC 60950-1 |
CE In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC |
Galvanic Isolation Input to Output: 3.0KVac Input to Ground: 2.0KVac Output to Ground: 0.5KVac |
Emission Generic Standards: EN 61000-6-3, EN 61000-6-4 CISPR 22, EN 55022, EN 55011, FCC Title 47: Class B; GB9254.1 |
Harmonic Current Emissions IEC/EN 61000-3-2, Class A; GB17625.1 |
Voltage Fluctuation and Flicker IEC/EN 61000-3-3 |